Voltage drop example question
You have a PV array in a field and an inverter at a house 250 feet away. You are
using 10AWG stranded copper wire. There is just one string and the voltage of
the string operates at Vmp of 200V and an Imp of 5A. What is the percentage
power loss due to dc voltage drop?
Answer
Voltage drop is calculated with Ohm’s Law, which states:
Vdrop = I X R
We know that current is I = 5A
We will solve for resistance by multiplying:
ohm / kFT X kFT = ohm
The distance from the PV to the inverter is 250 feet, so there will be two wires
to complete the circuit, therefore the wire length is:
250 feet X 2 directions = 500 feet
500 feet / 1000 feet per kFT = 0.5kFT
Distance = 0.5kFT
From looking up the properties of 10AWG stranded copper wire, we get
1.24 ohms/kFT, so:
ohm / kFT X kFT = ohm
1.24 ohms / kFT X 0.5 kFT = 0.62 ohm
Resistance = 0.62 ohm
Now back to Ohm’s Law:
Vdrop = I X R
Vdrop = 5A X 0.62 ohm
Vdrop = 3.1 volts
We now know that during peak sun conditions, we are losing 3.1 volts on the
wire and if we measured the voltage at the array, it would be 3.1 volts higher
than at the inverter.
To figure out our losses as a percentage we will divide voltage drop by system
voltage and then turn that into a percentage.
(Vdrop / system voltage) X 100% = voltage drop percentage
(3.1V / 200V) X 100% = 1.55% voltage drop
Since voltage multiplied by current is power, then voltage drop percentage is the
same as power loss, so we are losing 1.55% of our power in this case.